| Generator Model | GJY600-NG | |
| Gas Source | Natural Gas | |
| Standby kVA | 1000 | |
| Prime kVA | 750 | |
| Standby kW | 800 | |
| Prime kW | 600 | |
| RPM | (r/min) | 1500 |
| Voltage Options | V | 400 |
| Frequency | 50 | |
| Power Factor | 0.8 | |
| Electrical Efficiency | % | ≥38 |
| Thermal Efficiency | % | ≥54.8 |
| Total Efficiency | % | ≥92.8 |
| Gas Consumption | m³/h | 173.5 |
| Heat balance parameters | ||
| Cylinder Liner Cooling Water Heat (±8%) | kW | 425 |
| Oil Cooler Cooling Water Heat (±8%) | kW | 115 |
| Total Cooling Water Heat of High Temperature Cooling System (±8%) | kW | 540 |
| Intercooler Cooling Water Heat (±8%) | kW | 166 |
| Total Cooling Water Heat of Low Temperature Cooling System (±8) | kW | 166 |
| Exhaust Gas Waste Heat (exhaust gas temperature up to 120°C) (±8%) | kW | 355 |
| Total Radiant Heat (±8%) | kW | 65 |
| Cooling parameters | ||
| High temperature circulation water flow rate | m³/h | 52.2 |
| High Temperature Circulation Water Inlet Temperature (±2%) | °C | 77.1 |
| Outlet temperature of high temperature circulating water (±2%) | °C | 86 |
| Low temperature inlet water temperature (±2%) | °C | 40 |
| Low temperature outlet water temperature (±2%) | °C | 42.4 |
| Intake and exhaust parameters | ||
| Air Intake | kg/h | 3,246 |
| Gas Intake | kg/h | 132 |
| Air Displacement | kg/h | 3,378 |
| Exhaust temperature after turbocharger (±5%) | °C | 460 |
| Test Conditions | ||
| Calorific value of gas | kWh/m | 9.1 |
| Methane volume content | % | ≥96 |
| Gas temperature | °C | -10~40°C |
| Gas inlet pressure (Before regulator) | kPa | 30~50 |
| Gas inlet pressure (After regulator) | kPa | 8~15 |
| Air intake negative pressure | kPa | >-3 |
| Exhaust back pressure | kPa | <5 |
| Absolute atmospheric pressure | kPa | 101.32 |
| Ambient temperature | °C | 25 |
| Relative humidity | % | 30 |
| Altitude | m | ≤1,000 |