Generator Model | GJY100-NG | |
Gas Source | Natural Gas | |
Standby kVA | 137.5 | |
Prime kVA | 125 | |
Standby kW | 110 | |
Prime kW | 100 | |
RPM | (r/min) | 1500 |
Voltage Options | V | 400 |
Frequency | 50 | |
Power Factor | 0.8 | |
Electrical Efficiency | % | ≥38 |
Thermal Efficiency | % | ≥48.5 |
Overall Efficiency | % | ≥86..5 |
Gas Consumption | m³/h | 28.9 |
Heat balance parameters | ||
Cylinder liner cooling water heat (±8%) | kW | 140 |
Oil cooler cooling water heat (±8%) | kW | 38 |
Total cooling water heat of high temperature cooling system (±8%) | kW | 178 |
Intercooler cooling water heat (±8%) | kW | 32 |
Total cooling water heat of low temperature cooling system (±8%) | kW | 32 |
Exhaust gas waste heat (exhaust gas temperature up to 120°C) (±8%) | kW | 113 |
Total radiant heat (±8%) | kW | 20 |
Cooling parameters | ||
High temperature circulation water flow rate | m³/h | 8.3 |
High temperature circulation water inlet temperature (±2%) | °C | 78.6 |
High temperature circulation water outlet temperature (±2%) | °C | 85 |
Low temperature inlet water temperature (±2%) | °C | 50 |
Low temperature outlet water temperature (±2%) | °C | 51.2 |
Intake and exhaust parameters | ||
Air intake | kg/h | 1164 |
Gas intake | kg/h | 48 |
Air displacement | kg/h | 1212 |
Exhaust temperature after turbocharger (±5%) | °C | 490 |
Test Conditions | ||
Calorific value of gas | kWh/m | 9.1 |
Methane volume content | % | ≥96 |
Gas temperature | °C | -10~40°C |
Gas Inlet Pressure (Before Regulator) | kPa | 800~1000 |
Gas Inlet Pressure (After Regulator) | kPa | 400~600 |
Air intake negative pressure | kPa | >-3 |
Exhaust back pressure | kPa | <5 |
Absolute atmospheric pressure | kPa | 101.32 |
Ambient temperature | °C | 25 |
Relative humidity | % | 30 |
Altitude | m | ≤1,000 |