Generator Model | GJY2000-NG | |
Gas Source | Natural Gas | |
Standby kVA | 2750 | |
Prime kVA | 2500 | |
Standby kW | 2200 | |
Prime kW | 2000 | |
RPM | (r/min) | 1500 |
Voltage Options | V | 400 – 3300 – 6000 – 6300 – 6600 – 10000 – 10500 – 11000 |
Frequency | 50 | |
Power Factor | 0.8 | |
Electrical Efficiency | % | ≥40 |
Thermal Efficiency | % | ≥52.3 |
Total Efficiency | % | ≥92.3 |
Gas Consumption | m³/h | 515.5 |
Heat balance parameters | ||
Cylinder liner cooling water heat (±8%) | kW | 699 |
Oil cooler cooling water heat (±8%) | kW | 340 |
High temperature cooling system total cooling water heat (±8%) | kW | 1365 |
Intercooler cooling water heat (±8%) | kW | 326 |
Low temperature cooling system total cooling water heat (±8%) | kW | 148 |
Exhaust gas waste heat (exhaust gas temperature up to 120°C) (±8%) | kW | 1045 |
Total radiant heat (±8%) | kW | 150 |
Cooling parameters | ||
High temperature circulation water flow rate | m³/h | 120 |
High temperature circulation water inlet temperature (±2%) | °C | 74.8 |
Outlet temperature of high temperature circulating water (±2%) | °C | 86 |
Low temperature inlet water temperature (±2%) | °C | 40 |
Low temperature outlet water temperature (±2%) | °C | 41.5 |
Intake and exhaust parameters | ||
Air intake | kg/h | 10,345.9 |
Gas intake | kg/h | 384.5 |
Air displacement | kg/h | 10,730.4 |
Post-turbocharger exhaust temperature (±5%) | °C | 480 |
Test Conditions | ||
Calorific value of gas | kWh/m | 9.7 |
Methane volume content | % | ≥96 |
Gas temperature | °C | -10~40°C |
Gas inlet pressure (Before regulator) | kPa | 30~50 |
Gas inlet pressure (After regulator) | kPa | 8~15 |
Air intake negative pressure | kPa | >-3 |
Exhaust back pressure | kPa | <5 |
Absolute atmospheric pressure | kPa | 101.32 |
Ambient temperature | °C | 25 |
Relative humidity | % | 30 |
Altitude | m | ≤1,000 |