| Generator Model | GJY2000-NG | |
| Gas Source | Natural Gas | |
| Standby kVA | 2750 | |
| Prime kVA | 2500 | |
| Standby kW | 2200 | |
| Prime kW | 2000 | |
| RPM | (r/min) | 1500 |
| Voltage Options | V | 400 – 3300 – 6000 – 6300 – 6600 – 10000 – 10500 – 11000 |
| Frequency | 50 | |
| Power Factor | 0.8 | |
| Electrical Efficiency | % | ≥40 |
| Thermal Efficiency | % | ≥52.3 |
| Total Efficiency | % | ≥92.3 |
| Gas Consumption | m³/h | 515.5 |
| Heat balance parameters | ||
| Cylinder liner cooling water heat (±8%) | kW | 699 |
| Oil cooler cooling water heat (±8%) | kW | 340 |
| High temperature cooling system total cooling water heat (±8%) | kW | 1365 |
| Intercooler cooling water heat (±8%) | kW | 326 |
| Low temperature cooling system total cooling water heat (±8%) | kW | 148 |
| Exhaust gas waste heat (exhaust gas temperature up to 120°C) (±8%) | kW | 1045 |
| Total radiant heat (±8%) | kW | 150 |
| Cooling parameters | ||
| High temperature circulation water flow rate | m³/h | 120 |
| High temperature circulation water inlet temperature (±2%) | °C | 74.8 |
| Outlet temperature of high temperature circulating water (±2%) | °C | 86 |
| Low temperature inlet water temperature (±2%) | °C | 40 |
| Low temperature outlet water temperature (±2%) | °C | 41.5 |
| Intake and exhaust parameters | ||
| Air intake | kg/h | 10,345.9 |
| Gas intake | kg/h | 384.5 |
| Air displacement | kg/h | 10,730.4 |
| Post-turbocharger exhaust temperature (±5%) | °C | 480 |
| Test Conditions | ||
| Calorific value of gas | kWh/m | 9.7 |
| Methane volume content | % | ≥96 |
| Gas temperature | °C | -10~40°C |
| Gas inlet pressure (Before regulator) | kPa | 30~50 |
| Gas inlet pressure (After regulator) | kPa | 8~15 |
| Air intake negative pressure | kPa | >-3 |
| Exhaust back pressure | kPa | <5 |
| Absolute atmospheric pressure | kPa | 101.32 |
| Ambient temperature | °C | 25 |
| Relative humidity | % | 30 |
| Altitude | m | ≤1,000 |