| Generator Model | GJY300-NG | |
| Gas Source | Natural Gas | |
| Standby kVA | 400 | |
| Prime kVA | 375 | |
| Standby kW | 320 | |
| Prime kW | 300 | |
| RPM | (r/min) | 1500 |
| Voltage Options | V | 400 |
| Frequency | 50 | |
| Power Factor | 0.8 | |
| Electrical Efficiency | % | ≥38 |
| Thermal Efficiency | % | ≥54.1 |
| Total Efficiency | % | ≥92.1 |
| Gas Consumption | m³/h | 86,8 |
| Heat balance parameters | ||
| Cylinder liner cooling water heat (±8%) | kW | 220 |
| Oil cooler cooling water heat (±8%) | kW | 54 |
| Total cooling water heat of the high temperature cooling system (± 8%) | kW | 275 |
| Intercooler cooling water heat (±8%) | kW | 79 |
| Total cooling water heat of the low temperature cooling system (± 8) | kW | 79 |
| Exhaust gas waste heat (up to 120°C exhaust gas temperature) (±8%) | kW | 177 |
| Total radiant heat (±8%) | kW | 30 |
| Cooling parameters | ||
| Flow rate of high temperature circulating water | m³/h | 48 |
| Inlet temperature of high temperature circulating water (± 2%) | °C | 80,1 |
| Outlet temperature of high temperature circulating water (± 2%) | °C | 85 |
| Low temperature inlet water temperature (±2%) | °C | 40 |
| Low temperature outlet water temperature (±2%) | °C | 42,3 |
| Intake and exhaust parameters | ||
| Air intake | kg/h | 1807,3 |
| Gas intake | kg/h | 70,7 |
| Air displacement | kg/h | 1,878 |
| Exhaust temperature after turbocharging (±5%) | °C | 425 |
| Test Conditions | ||
| Calorific value of gas | kWh/m | 9.1 |
| Methane volume content | % | ≥96 |
| Gas temperature | °C | -10~40°C |
| Gas Inlet Pressure (Before Regulator) | kPa | 800~1000 |
| Gas Inlet Pressure (After Regulator) | kPa | 400~600 |
| Air intake negative pressure | kPa | >-3 |
| Exhaust back pressure | kPa | <5 |
| Absolute atmospheric pressure | kPa | 101.32 |
| Ambient temperature | °C | 25 |
| Relative humidity | % | 30 |
| Altitude | m | ≤1,000 |