Generator Model | GJY1000-NG | |
Gas Source | Natural Gas | |
Standby kVA | 1375 | |
Prime kVA | 1250 | |
Standby kW | 1100 | |
Prime kW | 1000 | |
Rpm | (r/min) | 1000 |
Voltage Options | V | 400 – 3300 – 6000 – 6300 – 6600 – 10000 – 10500 – 11000 |
Frequency | 50 | |
Power Factor | 0.8 | |
Electrical Efficiency | % | ≥40 |
Thermal Efficiency | % | ≥51.3 |
Total Efficiency | % | ≥91.3 |
Gas Consumption | m³/h | 257.7 |
Heat balance parameters | ||
Cylinder Liner Cooling Water Heat (±%8) | kW | 328 |
Oil Cooler Cooling Water Heat (±%8) | kW | 197 |
Total Cooling Water Heat of High Temperature Cooling System (± %8) | kW | 664 |
Intercooler Cooling Water Heat (±%8) | kW | 139 |
Total Cooling Water Heat of Low Temperature Cooling System (± 8) | kW | 102 |
Exhaust Gas Waste Heat (Exhaust Gas Temperature Up to 120°C) (±%8) | kW | 621 |
Total Radiant Heat (±%8) | kW | 84 |
Cooling parameters | ||
Flow Rate of High Temperature Circulation Water | m³/h | 60 |
Inlet Temperature of High Temperature Circulation Water (± %2) | °C | 75.1 |
Outlet temperature of high temperature circulating water (±2%) | °C | 86 |
Low temperature inlet water temperature (±2%) | °C | 40 |
Low Temperature Outlet Water Temperature (±%2) | °C | 41.7 |
Intake and exhaust parameters | ||
Air Intake | kg/h | 5304.2 |
Gas Intake | kg/h | 202.5 |
Air Displacement | kg/h | 5506.7 |
Post-Turbocharger Exhaust Temperature (±%5) | °C | 485 |
Test Conditions | ||
Calorific value of gas | kWh/m | 9.7 |
Methane volume content | % | ≥96 |
Gas temperature | °C | -10~40°C |
Gas inlet pressure (Before regulator) | kPa | 30~50 |
Gas inlet pressure (After regulator) | kPa | 8~15 |
Air intake negative pressure | kPa | >-3 |
Exhaust back pressure | kPa | <5 |
Absolute atmospheric pressure | kPa | 101.32 |
Ambient temperature | °C | 25 |
Relative humidity | % | 30 |
Altitude | m | ≤1,000 |